an image

SR1 SLIM RELAY

1 CHANGE-OVER CONTACTS, SCREW CONTACTS

SR1 Relay

SR1 Relay
Circuit diagram

Circuit diagram

Electrical life AC load

Electrical life AC load

Max.DC breaking capacity

Max.DC breaking capacity

SR1 dimensions

SR1 dimensions

TECHNICAL APPROVALS

TYPE

SR1L …V

1 contact Slim Relay

DOWNLOADS

CONTACT

Max.Contact load 6A / 250V AC1
6A / 30V DC1
Material AgNi -Standard
Rated current 6 A
Max. peak current 15 A
Rated voltage 250 V
Max. switching voltage AC-1 250 A
Rated load AC15 (250 V) 350 VA
Min. switching load 10V / 10mA

COIL

Operation range ≤0,75 x UN – 1,3 x UN
Rated power (AC/DC) 1,5 VA /0,9 W
Release voltage ≥0,1xUN
Coil resistance ±10%

CONTROL IMPUT DATA

Input control voltage 24 -240 VAC/VDC
Input control current <30 mA
Power control 1.500 VA

INSULATION (Vrms, 1 min)

Contact open 1 KV
Coil /Contacts 4 KV
Insulation IEC 61810-1 2,5 KV /3
Between contacts 2 KV

SPECIFICATIONS

Ambient temperature -40 ºC … +60/85ºC
Operation time ≤8 ms
Release time ≤4 ms
Protection category IP40
Electrical life DC 1-105 op
Mechanical life 10-105 op [AC] 20-106op [DC]

TECHNICAL APPROVALS